[technical analysis] causes of high surface temperature of water cooled condenser

visits:62 addtime:2023-10-11 16:37:33

n the working process of the refrigeration system, the temperature of the outer surface of the water-cooled stage condenser should be close to the normal temperature, and the hands should not feel hot. Once the surface temperature is too high, the cause should be found out and measures should be taken to eliminate this phenomenon.


Generally speaking, the main cause of condenser temperature rise is the problem of cooling water. There are usually four kinds of feelings


Situation:


1) There is not enough cooling water and water pressure. The water-cooled condenser uses cooling water to take away the latent heat released during the condensation of refrigerant vapor. Therefore, the pressure of cooling water is not enough, the flow rate can not meet the rated requirements, and the heat dissipation capacity is limited, * which eventually causes the surface temperature of the condenser to rise.


2) The cooling water temperature is too high, which is higher than the rated operating temperature (usually 32 ℃). The cooling water temperature in Vietnam, the smaller the cooling temperature difference of refrigerant, the smaller the heat transfer, the refrigerant can not be effectively cooled, and the surface temperature of condenser will rise


High.


3) The poor quality of cooling water leads to scaling on the inner wall of the cooling water pipe in the condenser, increasing the thermal resistance, affecting the heat exchange between refrigerant and cooling water, and reducing the heat transfer effect. This kind of fault often occurs in the equipment which has been used for a long time and has not been cleaned regularly. The solution is to remove scale.


4) The inlet and outlet pipes of cooling water are installed incorrectly. The normal installation position is generally low inlet pipe position and high outlet pipe position


"Low in, high out.". If the inlet pipe is set high, the cooling water can not be completely filled in the condenser, the heat transfer area will be smaller, and the refrigerant vapor can not be effectively condensed, which will make the surface temperature of the condenser rise.


When the surface temperature of the condenser increases, it means that the condensation effect is recommended, and the cooling capacity of the system will decrease.


主站蜘蛛池模板: 成人免费a级毛片无码片在线播放 | 99久久人人爽亚洲精品美女 | 无码人妻精品一区二区三区66 | 一本久道久久综合狠狠爱 | 欧美午夜精品久久久久久软件 | 欧美极品日韩极品1 | 欧美日韩精品码免费专区 | 99re在线视频 | 高h猛烈失禁潮喷无码视频 JIZZJIZZ国产精品久久 | 成年人在线视频 | 亚洲成人一区二区在线观看 | 国产91对白叫床清晰播放 | 黄色免费在线视频 | 8888在线观看免费www | 成人毛片久久 | 中文字幕久久久人妻无码 | 国产精品乱子伦XXXX | 国产精品色区在线观看 | 国语自产少妇精品视频蜜桃 | 国产成人专区 | 久久国产精品网站 | 神马老子影院午夜观看网站 | 亚洲一区二区三区三 | 国产精品人妻熟女毛片av | 久久我不卡 | 国产成人av免费 | 欧美在线一区二区三区 | 久久久久久国产精品久久 | 久久免费网 | 久草在线欧美 | 91香草视频 | 日韩av无码精品人妻系列 | 一级特黄免费 | 亚洲精品国产精品久久 | 日韩精品一区二区三区四区在线观看 | 人人爽亚洲AV人人爽AV人人片 | 国产成人精品一区二区三 | 亚洲第一视频在线 | 欧美人与动牲交片免费 | 美欧日韩av无码一区二区 | 视频一区二区三区波多野结衣 |